| Part Number : 372D522G02-374D212G0 | Manufacturer : Westinghouse Electric Corp | ||
| NSN : 5925-01-124-9624 (5925011249624) | |||
| Item Name : Circuitbreaker | CAGE Code : 11660 | ||
| NIIN : 01-124-9624 (011249624) | |||
| FSC Code : 5925 Circuit Breakers | |||
| FSG Code : 59 Electrical and Electronic Equipment Components | |||
| INC Code : 00136 | |||
| NCB Code : 01 | Country : USA | ||
| Alternate P/N: 372D522G02374D212G0 | |||
Thank you for taking an interest in part number 372D522G02-374D212G0, that of which is listed with the description Circuitbreaker; Manufactured by Westinghouse Electric Corp and listed alongside the NSN 5925011249624, part number 372D522G02-374D212G0 is available for immediate purchase on our website. As such, to learn more about this offering while receiving a competitive quote for your comparisons, be sure to fill out and submit the RFQ form presented on this page. Within 15 minutes of us receiving and reviewing a completed form, a member of our staff will contact you to present a tailored solution for your comparisons.
|
3dbm co inc
CAGE Code: 31791,62874 |
3m france
CAGE Code: F0347 |
|
331 l tech productions llc
CAGE Code: 01XA0 |
3 wire group inc
CAGE Code: 4X0B1,7VME3 |
|
3m aerospace
CAGE Code: R0844 |
101communications inc
CAGE Code: 1WS16 |
|
2kr systems llc
CAGE Code: 730Z2 |
2101 llc
CAGE Code: 1GH76 |
|
3dfx interactive
CAGE Code: KA796 |
2056 company
CAGE Code: 7F967 |
|
3gen corporation
CAGE Code: 3SPS3 |
3m italia spa
CAGE Code: A3445 |
|
3m united kingdom plc
CAGE Code: K0993,K8767 |
136963 canada inc
CAGE Code: 3AD36 |
|
3m health care service center
CAGE Code: 0UTW7 |
| Part Number : 372D522G02-374D212G0 | Manufacturer : Westinghouse Electric Corp | ||
| NSN Number : 5925-01-124-9624 (5925011249624) | |||
| Item Name : Circuitbreaker | CAGE Code : 11660 | ||
| NIIN : 011249624 | |||
| FSC CODE : 5925 Circuit Breakers | |||
Thank you for taking an interest in part number 372D522G02-374D212G0, that of which is listed with the description Circuitbreaker; Manufactured by Westinghouse Electric Corp and listed alongside the NSN 5925011249624, part number 372D522G02-374D212G0 is available for immediate purchase on our website. As such, to learn more about this offering while receiving a competitive quote for your comparisons, be sure to fill out and submit the RFQ form presented on this page. Within 15 minutes of us receiving and reviewing a completed form, a member of our staff will contact you to present a tailored solution for your comparisons.
| NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
|---|---|---|---|---|---|---|
| 5925-01-124-9624 Item PartTypeName: CIRCUIT BREAKER | 5925 | 011249624 | P | |||
| CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
| A | 0 | |||||
| Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
| 372D522G02-374D212G0 | 5 | 1 | C | A |
| MRC | Criteria | Characteristic |
|---|---|---|
| AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| ADAQ | BODY LENGTH | 22.000 INCHES NOMINAL |
| ADAT | BODY WIDTH | 12.000 INCHES NOMINAL |
| ADAU | BODY HEIGHT | 12.243 INCHES NOMINAL |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 14.375 INCHES NOMINAL |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 4.000 INCHES NOMINAL |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 13.625 INCHES NOMINAL |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 4.000 INCHES NOMINAL |
| AJEC | BOSS HEIGHT | 0.813 INCHES NOMINAL |
| AKPX | POLE QUANTITY | 3 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED STUD |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CBBL | FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
| CMLP | THREAD QUANTITY PER INCH | 16 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 1200.0 AMPERES AC ALL LOCATIONS |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC ALL LOCATIONS |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 50000.0 AC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 140.0 ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| CPSF | ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | 2000.0 TO 6000.0 AC ALL LOCATIONS |
| CQJX | NOMINAL THREAD SIZE | 0.375 INCHES |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.041 MINIMUM AT 200 PCT AND 0.045 MAXIMUM AT 200 PCT ALL LOCATIONS |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| CWJK | CASE MATERIAL | PLASTIC |
| FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| THSD | THREAD SERIES DESIGNATOR | UNC |
| TTQY | TERMINAL TYPE AND QUANTITY | 6 QUICK DISCONNECT,MALE |